Technical Datasheet Archive

Streamline your submittal process with our complete technical archive.

Quickly locate the exact data sheets and certification documents you need for your project requirements.

UL/ULC Fire Detection and Alarm System

FW2105 UL Intelligent Fire Alarm Control Panel

 

DESCRIPTIONS

The FW2105 is an intelligent Fire Alarm Control Panel (FACP) designed for small to medium-scale facilities. The FW2105 is ideally suited for both new and retrofit commercial, institutional, and industrial fire detection and notification applications. The FW2105 is a state-of-art addressable fire control system that meets the requirements of UL 864, and CAN/ULC-S527. It can support up to 9 Signaling Line Circuits and 2268 addressable devices/points, 12 Notification Appliance Circuits and 4 form C dry relay contacts. The panel has a 7” color LCD and a resolution of 800×480 pixels screen, 6 auxiliary function keys and 12 LED indicators making it a highly intuitive fire alarm user interface.

The FW2105 can connect with up to 32 remote annunciators via an ANU to form a fire emergency detection and notification network system.

KEY FEATURES

  • Up to 9 Signaling Line Circuits and 2268 addressable devices/points
  • Up to 12 Notification Appliance Circuits
  • 4 form C dry relay contacts
  • 8 Isolated SLC circuits
  • A 7” color LCD with 800×480 resolution
  • 12 LED indicators , 6 auxiliary function keys
  • 1000+5000 events historical log
  • Single-phase earth fault detection
  • Manual alarm function
  • PAS (Positive Alarm Sequence) function
  • Two-Stage alarm function
  • Silent inhabit function, 0~20 min available.
  • Trouble/Supervisory Resound

FW2121 UL Remote LCD Annunciator

 

DESCRIPTIONS

The FW2121 fire display panel is used to repeatedly display the fire alarm information on the floor or independent fire prevention area. The FW2121 is installed in the floor or the independent fire prevention area, which can receive the fire alarm information of the loop, across the loop and across the machine and make the corresponding alarm prompt.

KEY FEATURES

  • Intelligent remote LCD annunciator
  • Class A and Class B circuits available
  • LCD display with 320×80 resolutions
  • Fully icon indications and intuitive fire alarm
  • Display annunciate up to 8 zones simultaneously

FW2129 UL Remote LED Annunciator

 

DESCRIPTIONS

The Led Annunciator are used to display zone events which are from FACP FW2105 /FW2107. LED Annunciator include two types: Local Annunciator FW2261 and Remote Annunciator FW2129.

KEY FEATURES

  • 4 options:1 bay,2 bay,3 bay and 5 bay
  • 4 button functions
  • 8 slots per bay, 8 modules

FW2511 UL Addressable Smoke Detector

 

DESCRIPTIONS

The FW2511 is an intelligent Smoke Detector. It’s certified with UL 268, 7th edition and ULC-S529 which passes flaming and smoldering polyurethane tests, as well as the Cooking Nuisance test. The Maple Armor’s new detection technology helps to reduce nuisance alarms and improve reliability of fire detection.

KEY FEATURES

  • Photo Electric smoke detector with dual light source
  • Embedded Microcontroller Unit for self-diagnostic tests and result analysis
  • Two Led lights allow for 360° viewing
  • 3-level alarm sensitivity
  • 3 base options, FW2501 (4’’), FW2502(6’’), FW2509 (sounder base)

FW511 UL/FM Addressable Smoke Detector

 

DESCRIPTIONS

 

KEY FEATURES

FW2521 UL Addressable Heat Detector

 

DESCRIPTIONS

The FW2521 is an intelligent Heat Detector for indoor use with both fixed-temperature alarm and rate-of-rise alarm characters. It features a slim design, which combines visual appeal with a high standard of reliability. The detector has a Microcontroller Unit (MCU) performing comprehensive

Self-diagnostic tests, and result analysis.

KEY FEATURES

  • Combined heat detection: Fixed / Rate-of-Rise (ROR)
  • Embedded Microcontroller Unit for self-diagnostic tests and result analysis
  • Two Led lights allow for 360° viewing
  • IP33 rating, with the optimal performance under condensation when using together with MA-BWA-S.

FW521 UL/FM Addressable Heat Detector

 

DESCRIPTIONS

 

KEY FEATURES

FW2509 UL Sounder Base

 

DESCRIPTIONS

The FW2509 is designed for use with Maple Armor detector heads or equivalent and is intended to provide occupant notification in fire events within the protected space. It meets the needs of dwelling unit applications. The FW2509 can produce multiple tone patterns including temporal 3, temporal 4, continuous, 20bpm, 60bpm and 120 bpm required by NFPA 72 for commercial and residential applications. 7 levels of sound outputs are selectable. The FW2509 can be commanded by the Fire Alarm Control Panel. The panel can command an individual FW2509, or a group of FW2509 by pre-programming. FW2509 does not take address on SLC.

KEY FEATURES

  •  

FW272X Series UL Intelligent Manual Pull Station

 

DESCRIPTIONS

FW2721 Dual Action, Single Stage Addressable Manual Pull Station
FW2722 Two Stage Addressable Manual Pull Station
FW2723 Single Action, Single Stage Addressable Manual Pull Station

The FW272X series addressable Manual Pull Stations are UL listed devices according to UL 38 and ULC-S528 for Fire Protective Signaling Systems for indoor use. They made from durable materials and solid parts for long lasting performance.

The 272X series occupy a single address on the ALU and transmit alarm event status to the panel when activated. The 272X series contain dry contact with normally open or normally close options available.

KEY FEATURES

  • Dual action station
  • Addressable
  • PUSH HERE and PULL DOWN
  • Status LED Indicator
  • Easy to use reset key
  • Included dry contact (2A, 24VDC)
  • Two Dry contact options (N/O or N/C)

FW2961 UL Addressable/ Conventional Horn Strobe

 

DESCRIPTIONS

 

 

KEY FEATURES

  •  

FW2971 UL Addressable/ Conventional Horn

 

DESCRIPTIONS

 

 

KEY FEATURES

  •  

FW29XX Series Addressable Horn Strobe

 

DESCRIPTIONS

The FW2961 Horn Strobe, FW2971 Horn, and FW2981 Strobe are a family of visual and audible signal appliances with light sources generated from white LED, listed according to UL 1971, UL 1638, UL 464, ULC-S525 and ULC-S526 for indoor use.

These appliances can operate in both conventional and addressable modes, offering flexibility in system design and implementation. Six levels of light output, seven levels of sound outputs are selectable.

The appliance has the feature that can synchronize multiple horn and/or strobes based on loop.

KEY FEATURES

Horn features

  • Conventional or addressable
  • Seven levels of sound pressure settings
  • Switchable buzzer tones
  • Built-in synchronization

Strobe features

  • Multi candela LED Strobe: 15,30,75,110,140,177 cd
  • Six levels light intensity settings
  • High-intensity LED light source
  • Built-in synchronization

FW2811 UL Addressable Input Module

 

DESCRIPTIONS

The FW2811 input module monitors a single contact. The input line is monitored for open line faults and ground faults, and the contact must thus be wired with an end-of-line resistor. It is an intelligent addressable module and takes one address on SLC or Data Communication Link (DCL) of the fire alarm control panel.

The FW2811 is a UL listed device according to UL864 and ULC-S527 and the type of the input contact is configurable for 4 types:

  • Alarm
  • Supervisory
  • Trouble
  • Monitor or feedback

KEY FEATURES

  •  

FW2821 UL Addressable Input/Output Module

 

DESCRIPTIONS

FW2821 is an intelligent input-output module for fire protective signaling systems for indoor use. The FW2821 is an intelligent addressable module and takes one address on the SLC or DCL of the FACP. The FW2821 offers a single 24VDC output and an input switch. It monitors for open line faults and ground faults on the input side, while on the output side, it keeps track of open line, short circuit, ground faults, and the loss of the external 24VDC power source. Input switch can be configurable for 4 types:

  • Alarm
  • Supervisory
  • Trouble
  • Monitor or feedback

KEY FEATURES

  •  

FW2831 UL Addressable Relay Module

 

DESCRIPTIONS

The FW2831 relay module provides two control relay outputs, which will be activated simultaneously. When the outputs are activated, the device LED will indicate the event condition by red steady on. A return to normal condition will cause the event to disappear and the device LED indicator will return to red every 4 seconds.

  • Intelligent addressable module
  • Two control relay outputs
  • LED indicator
  • SLC/DCL Class A or Class B

KEY FEATURES

  •  

FW2841 UL Addressable Conventional Zone Module

 

DESCRIPTIONS

The FW2841 conventional zone module is intended to allow Maple Armor intelligent fire alarm control panels to interface and monitor 2-wire conventional detectors in retrofit applications. The initiating zone can support a mix of 2-wire conventional automatic detectors as well as normally open dry contact alarm initiating devices.

  • Conventional module
  • Supports a zone of up to 32 conventional smoke detectors
  • Compatible with Class B and Class A wiring

KEY FEATURES

  •  

FM Aspirating Smoke Detector

FW2601 FM PipeSense Aspirating Smoke Detector

 

DESCRIPTIONS

The FW2601 series aspirating smoke detector offers abundant pipeline configurations. Each pipeline has an independent detection chamber to ensure reliable high-sensitivity detection.

The default pipe addressing function and independent PT platinum airflow sensor for each pipe enhance the accuracy of detection and alarm. The advanced laser detection technology features high sensitivity, a wide sensitivity range, and good consistency. The extra-long pipe and abundant holes along the pipe ensure extensive coverage and effective detection.

The FW2601 utilizes micro-dust separation technology with improved immunity to false alarms and longer filter lifespan. It can record up to 20,000 events and it’s easy to integrate and interface with other systems.

KEY FEATURES

  • Available in 1/2/4 extra-long pipes
  • Modular based design and modular based replacement
  • Independent detection chamber for each pipe
  • Default pipe addressing
  • Independent airflow sensor for each pipe
  • High sensitivity laser detection
  • 4-level programmable alarm level
  • Micro-dust separation technology
  • Event log capacity up to 20,000

FW2601 FM Series

 

DESCRIPTIONS

The FW2601 series aspirating smoke detector offers abundant pipeline configurations. Each pipeline has an independent detection chamber to ensure reliable high-sensitivity detection.

The default pipe addressing function and independent PT platinum airflow sensor for each pipe enhance the accuracy of detection and alarm. The advanced laser detection technology features high sensitivity, a wide sensitivity range, and good consistency. The extra-long pipe and abundant holes along the pipe ensure extensive coverage and effective detection.

The FW2601 utilizes micro-dust separation technology with improved immunity to false alarms and longer filter lifespan. It can record up to 20,000 events and it’s easy to integrate and interface with other systems.

KEY FEATURES

  • Available in 1/2/4 extra-long pipes
  • Modular based design and modular based replacement
  • Independent detection chamber for each pipe
  • Default pipe addressing
  • Independent airflow sensor for each pipe
  • High sensitivity laser detection
  • 4-level programmable alarm level
  • Micro-dust separation technology
  • Event log capacity up to 20,000

UL Voice Alarm and Fire Telephone system

FW151 UL Digital Voice Control Panel

 

DESCRIPTIONS

The digital voice control panel is an intelligent emergency voice evacuation system designed for small and medium-scale facilities. The FW151 digital voice control panel is ideally suited for both new and retrofit commercial, institutional, and industrial applications. The FW151 digital voice control panel is a digital communication system that meets the requirements of UL 864 in the 10th Edition and CAN/ULC-S527 in the 3rd edition.

KEY FEATURES

  • 4.3” full color TFT LCD, Simple and easy to use operation interface
  • Up to 128 zone selector buttons and 256 zone indicators per DCP making it a highly intuitive fire alarm user interface
  • Indication of all required fault conditions
  • Digitized voice capability
  • Master microphone and telephone handset can be monitored by the master panel.

FW151-FP UL Digital Voice Control Panel

 

DESCRIPTIONS

FW151-FP is a modalized fire telephone control system, which contains the fire telephone related components from Maple Armor BlazeCom™series voice control system.

The master display unit contains full color 4.3” LCD, 8 LEDs for signal status, 8 LEDs for system status, 8 functional buttons, 24 buttons logical input keypad, 1 buzzer and 1 master microphone.

KEY FEATURES

  • 4.3” full color TFT LCD, Simple and easy to use operation interface
  • Up to 64 zone selector buttons and 128 zone indicators per DCP making it a highly intuitive fire alarm user interface
  • Master microphone and telephone handset can be monitored by the master panel.
  • Additional 4 conventional telephone wall jacks (FW864) can be connected to each addressable telephone wall jacks (FW864A) and are intended to be installed in the same zone.

UL/FM Addressable Fire Extinguishing System

FW2107 UL Fire Alarm Control Panel/ Agent Releasing Panel

 

DESCRIPTIONS

FW2107 is an Intelligent Fire Alarm Control Panel (FACP) designed for small and medium-scale facilities. The FACP is ideally suited for both new and retrofit commercial, institutional, and industrial fire detection and notification applications. It is with dual hazard agent releasing that meets the requirements of UL 864, and CAN/ULC-S527.

The FACP supports up to 252 devices, 2 NACs and 3 Form-C relays (pre-programmed for Alarm, Trouble and Supervisory). In addition, the control panel can be used for hazard agent releasing application via the SLC loop.

KEY FEATURES

  • 1 Signaling Line Circuits and 252 addressable devices/points
  • Up to 2 Notification Appliance Circuits
  • 3 form C dry relay contacts
  • 16 built in annunciator zones
  • Up to 2 releasing zone
  • A 2.8” true color LCD
  • Up to 16 zone LED annunciator

FW2731 UL Manual Release

 

DESCRIPTIONS

The FW2731 Manual Release is designed for use with Fire Alarm Control Panel that include agent release capability. It’s for indoor use and is constructed using durable materials and solid components to ensure long-lasting performance.

KEY FEATURES

  • Single action station
  • Addressable
  • Status LED Indicator
  • Easy to use reset key
  • Two Dry contact options (N/O or N/C)

FW2732 UL Abort Switch

 

DESCRIPTIONS

The FW2732 Abort Switch is designed for use with Fire Alarm Control Panel that include agent release capability. It is a single action Abort Switch. When the releasing zone FW2107 enters the alert or pre-discharge state, pressing and holding the abort switch will cancel the sequence for releasing the agent. The LED flashes once every 4 seconds in normal standby condition, and turn steady on when press.

KEY FEATURES

  • Addressable single action
  • Abort Switch 
  • Status LED Indicator

LPCB Addressable Fire and Alarm System

VI-6947 LPCB Intelligent Addressable Fire Alarm Control Panel

 

     

DESCRIPTIONS

  • Addressable fire alarm control panel LPCB approved to EN 54-2 and EN 54-4
  • 7-inch touch screen and touch-sensitive buttons is used for HMI and 18 LED for status indication
  • Support Class A loop wiring mode and Class B star wiring mode
  • Maximum 4 detection loops, each loop has 256 addressable devices in Class A mode or Switch to 512 addressable devices in Class B mode
  • 36 Zone indication for Fire, Fault, Disable
  • V-6847 has passed the optional requirement of EN54-4 that It can control FPE equipment, and detecting fault status from FPE.(Fire protection equipment such as: Water system, ventilation system, fire extinguish system etc.)
  • 2 Programmable sounder output terminal for conventional sounder.
  • 6 Programmable output for FPE device
  • 24V/3AAuxiliary power supply output for remote device
  • An additional NET card can enable networking through CANbus
  • True peer-to-peer(P2P) networking, it can support up to 128 FACPs
  • (V-6847) being interconnected
  • It is possible to preview the status of the entire fire alarm system through any FACP within this network

KEY FEATURES

AC Main Power                 3.0A@100~120VAC,50/60Hz
Standby Current              ≤1.5Al Max.a En54-4
Alarm Current                  ≤2.5AI Max.b En54-4
Battery                              The enclosure of panel can accommodate two                                            standard-sized 12V/7AH batteries connected                                            in series
Temperature Range         -10℃~50℃
Humidity                           ≤95%RH,(40±2℃)No condensat ion
Loop                                  Default 1 loop with 512 points
                                           Maximum 4 loop with 2048 points
Sounder Output               2 Programmable conventional sounder output.                                            Rated @1 amp each
Pro I/O                               Output Needs VI-6159 Terminal box for                                                       Programmable Remote VO control
Alarm Output Relay         1A at 30VDC
Fault Output Relay           1A at 30VDC
Network                             CANbus, Baudrate
Dimension                         480x355x120mm

VI-6627 LPCB Addressable Smoke Detector

 

     

FEATURES

  • Addressable Smoke Detector
  • Advanced embedded Micro Controller Unit (MCU)
  • Drift compensation and dirty notification on fire alarm control panel
  • One LED for 360◦ visibility
  • Manual addressing via programmer
  • 4 sensitivity levels designed for different application environments
  • LPCB approved to EN54-7

TECHNICAL DATA

Operating Voltage:         16-28V (Modulated-pulse)
Standby Current:             ≤0.5mA
Alarm Current:                  ≤1.0 mA
Wiring:                               Two-wire (non-polarized)
Temperature Range:        -10°C ~ 50°C
Humidity:                           ≤95%RH, (40±2°C) No condensation
LED Alarm Indication:      Red light emitting
LED Polling Indication:     Red light flashing
Sensitivity Mode:              4
Installation Base               VB-6617

VI-6637 LPCB Addressable Heat Detector

 

     

FEATURES

  • Addressable Heat Detector
  • Advanced embedded Micro Controller Unit (MCU)
  • Dual-response mode A1R/A2
  • One LED for 360ᴼ visibility
  • Manual addressing via programmer
  • LPCB approved to EN54-5

TECHNICAL DATA

Operating Voltage:         16-28V (Modulated-pulse)
Standby Current:            ≤0.5mA
Alarm Current:                ≤1.0 mA
Wiring:                              Two-wire (non-polarized)
Temperature Range:       -10°C ~ 50°C
Humidity:                         ≤95%RH, (40±2°C) No condensation
LED Alarm Indication:    Red light emitting
LED Polling Indication:   Red light flashing
Respond Mode:              A1R/A2
IP Rating:                         IP32
Installation Base:            VB-6617

VI-6647 LPCB Addressable Multi-Sensor Detector

 

     

FEATURES

  • Addressable Multi-sensor Detector
  • Advanced embedded Micro Controller Unit (MCU)
  • Drift compensation and dirty notification on fire alarm control panel
  • Dual-response mode A1R/A2
  • Two LEDs for 360ᴼ
  • Manual addressing via programmer
  • LPCB approved to EN 54-5& EN 54-7

TECHNICAL DATA

Operating Voltage          16-28V (Modulated-pulse)
Standby Current             ≤0.5mA
Alarm Current                 ≤1.0 mA
Wiring                              Two-wire (non-polarized)
Temperature Range       -10°C ~ 50°C
Humidity                          ≤95%RH, (40±2°C) No condensation
LED Alarm Indication      Red light emitting
LED Polling Indication     Red light flashing
Respond Mode                A1R/A2
IP Rating                           IP32
Installation Base              VB-6617

VI-6657

VI-6657 LPCB Addressable Manual Call point

 

     

FEATURES

  • Addressable Manual Call Point
  • Advance embedded Micro Controller Unit (MCU)
  • The button ca be pressed in case of fire
  • Reset by a special key
  • LED Indication for operation status
  • Manual Addressing via programmer
  • Indoor use
  • LPCB approved to EN 54-11

TECHNICAL DATA

Operating Voltage          16-28V (Modulated-pulse)
Standby Current             ≤0.5mA
Alarm Current                 ≤1.0 mA
Wiring                               Two-wire (non-polarized)
Temperature Range       -10°C ~ 50°C
Humidity                          ≤95%RH, (40±2°C) No condensation
LED Alarm Indication      Red light emitting
LED Polling Indication     Red light flashing
Call Point Type                Type A-Direct operation
                                          (single action and resettable)
Call Point Principle          Operate by switch
IP Rating                           IP43

VI-6737 LPCB Addressable Sounder Beacon

 

     

FEATURES

  • Addressable Sounder Beacon
  • Type A : Indoor use
  • 4 Sounder output Levels
  • 16 tones for notification
  • Switchable Sounder/optical indication.
  • High-luminance LED
  • Manual addressing via programmer
  • Activated directly by loop voltage without AUX 24VDC
  • LPCB approved to EN 54-3

TECHNICAL DATA

Operating Voltage          16-28V (Modulated-pulse)
Standby Current             ≤0.3mA
Alarm Current                 ≤8 mA
Wiring                              Two-wire (non-polarized)
Temperature Range       -10°C ~ 50°C
Humidity                          ≤95%RH, (40±2°C) No condensation
LED Alarm Indication      Red light emitting
LED Polling Indication     Red light flashing
Tones                                16
IP Rating                           IP43
Installation Base              VB-6619

VI-6717 LPCB Addressable Monitor Interface

 

     

FEATURES

  • Addressable Input Monitor Module
  • Easy Installation
  • Input circuit line detection with EOL resistor
  • LPCB approved to EN 54-18:2005

TECHNICAL DATA

Operating Voltage          16-28V (Modulated-pulse)
Standby Current             ≤0.5mA
Alarm Current                 ≤1.0 mA
Wiring                              Two-wire (non-polarized)
Temperature Range       -10°C ~ 50°C
Humidity                          ≤95%RH, (40±2°C) No condensation
Operating Indication      Operate LED Flashing
Signal Input                      Action LED Emitting
Fault Indication               Operate LED Off
IP Rating                           IP32
Installation Base              VB-6618

VI-6727 LPCB Addressable Control Interface

       

FEATURES

  • Addressable Input and Output Module
  • Easy Installation
  • Output relay capacity: 30VDC/1A
  • Input circuit line detection with EOL resistor
  • LPCB approved to EN 54-18:2005

TECHNICAL DATA

Operating Voltage                                      16-28V (Modulated-pulse)
Standby Current                                         ≤0.5mA
Alarm Current                                             ≤1.0 mA
Wiring                                                          Two-wire (non-polarized)
Temperature Range                                   -10°C ~ 50°C
Humidity                                                     ≤95%RH, (40±2°C)                                                                                                   No condensation
Remote Control Output Indication         Output LED Emitting
Signal Inputting Indication                       Input LED Emitting
IP Rating                                                     IP32
Installation Base                                        VB-6618

VI-6777 LPCB Addressable Isolate Interface

 

     

FEATURES

  • Voltage-type isolation module
  • Loop power supply
  • Easy Installation
  • Dual isolate control
  • Supports both Class A and Class B wiring modes
  • LPCB approved to EN 54-17

TECHNICAL DATA

Operating Voltage           18-28V (Modulated-pulse)
Standby Current              ≤1mA
Isolate Holding Current   ≤10 mA
Action Condition             Isolate input/output side short circuit or                                                        loop voltage ≤7.5V
Temperature Range        -10°C ~ 50°C
Humidity                          ≤95%RH, (40±2°C) No condensation
Isolate Indication            Active A or Active B LED Emitting
IP Rating                           IP32
Installation Base              VB-6618

LPCB Conventional Fire and alarm system

VC-6831 LPCB Conventional Fire Alarm Control Panel

       

DESCRIPTIONS

  • High quality and reliable performance
  • 2/4/8/16 detection zone
  • Up to 25 devices for each zone
  • Up to 4 programmable supervised sounder circuits
  • LED indication and key buttons
  • One man walk-test and zone isolate facility
  • DAY/NIGHT mode switchable
  • Fault buzzer mute facility
  • Fully programmable using simple menu options
  • Keypad entry to a wide range of functions
  • Optional signal output board available for extension
  • Three access levels settable via a key switch
  • SMT and Microprocessor controller design
  • Two wire system to reduce cabling and installation
  • Compatible with wide range of conventional devices
  • LPCB approved to EN54-2 and EN54-4

KEY FEATURES

Power Supply                  AC220V/50Hz or AC110V/60Hz
Operating Voltage          15VDC~28VDC
Sounder Circuit              DC18V~28V, 300mA
Auxiliary Power               DC18V~28V, 500mA
Temperature Range        0ᴼC~40ᴼC
Humidity                          ≤95%RH, (40±2ᴼC) No condensation
Battery                             Two DC12V/7Ah
Installation                       Wall-mount
Dimension                        430*330*105mm

VC-6623 LPCB Conventional Smoke Detector

 

     

FEATURES

  • 360ᴼ visible LED
  • High performance on slow-burning or smoldering fire
  • Build-in program of Drift compensation
  • Intelligent algorithm and judgement
  • Special chamber against interference
  • Remote Indication Output
  • Magnetic test available
  • LPCB approved to EN54-7

TECHNICAL DATA

Operating Voltage          9DVC~28DVC
Quiescent Current          ≤60µA
Alarm Current                 10mA≤/≤50mA
Wiring                               Polarized two-wire
Temperature Range       -10ᴼC~+55ᴼC
Humidity                          ≤95%RH, (40±2ᴼC) No condensation
Alarm Indicator               Red Flashes periodically (2s – 4s) normally;                                                         lights steadily in alarm
Max Ripple Voltage         2V(peak-peak value)
Alarm Reset                     Instant power cut (2s Min, 1.0VDC Max)
IP Rating                           IP32
Installation Base              VB6611 

VC-6633 LPCB Conventional Heat Detector

 

     

FEATURES

  • 360ᴼ visible LED
  • Thermal sensor with high sensitivity
  • Classification of A2R
  • Principle of Fixed Temperature and Rate of Rise
  • Remote Indication Output
  • Talented plug-in structure without screw
  • Magnetic test available
  • LPCB approved to EN54-5

TECHNICAL DATA

Operating Voltage           9DVC~28DVC
Static Current                  ≤60µA
Alarm Current                  10mA≤/≤50mA
Wiring                               Polarized two-wire
Temperature Range        -10ᴼC~+55ᴼC
Humidity                          ≤95%RH, (40±2ᴼC) No condensation
Fire LED                            Red Flashes once every 2s-4s in normal state;                                                   Illuminates in alarm
Max Ripple Voltage         2V (peak-peak value)
Alarm Reset                     Instant power cut (2s Min, 1.0VDC Max)
IP Rating                           IP32
Installation Base              VB-6611

VC-6653 LPCB Conventional Manual Call point

       

FEATURES

  • Non-breaking and Resettable
  • Flush-mount or Wall-mount
  • Pluh-in structure and easy installation
  • Stylish appearance
  • Used in conventional line only
  • Indoor use
  • LPCB approved to EN 54-11

TECHNICAL DATA

Operating Voltage           24VDC (12VDC~28VDC)
Standby Current              ≤0.5mA
Alarm Current                  ≤20mA (equivalent resistance is 470Ὠ/1W)
Wiring                               Two-wire
Temperature Range       -10ᴼC~55ᴼC
Humidity                           ≤95%RH, (40±2ᴼC) No condensation
Indicator                           Red Illuminates after alarming
IP Rating                            IP43

VC-6734 LPCB Conventional Sounder Strobe

 

     

FEATURES

  • Audial and visual warning
  • 16 tones available
  • No external power supply required
  • Fast responding time and low power consumption
  • Plug-in structure and easy installation
  • Used in conventional sounder circuit only
  • LPCB approved to EN 54-3

TECHNICAL DATA

Operating Voltage          Power 24V (21V-28V)
Operating Current          Action Current ≤50mA
Flashing Frequency        1.4x(1±20%)Hz
Temperature Range        -10ᴼC~50ᴼC
Humidity                          ≤955RH, (40±2ᴼC) No condensation
IP Rating                           IP21C
Static Current                  ≤60µA
Alarm Current                 10mA≤/≤50mA
Wiring                               Polarized two-wire
Temperature Range        -10ᴼC~+55ᴼC
Humidity                          ≤95%RH, (40±2ᴼC) No condensation
Fire LED                           Red Flashes once every 2s-4s in normal state;                                                    Illuminates in alarm
Max Ripple Voltage        2V (peak-peak value)
Alarm Reset                     Instant power cut (2s Min, 1.0VDC Max)
IP Rating                           IP32
Installation Base              VB-6611

UL Exit and Emergency Light

TYI-P1000A UL Controller Operation Manual

 

FEATURES

  • Compliant with UL 924 for Emergency Lighting and Power Equipment.
  • State of the Art Touch Screen with 10-inch-wide display.
  • Each Panel can support up to 2040 luminaires.
  • 16320 luminaires on single Network
  • With Multiple communication bridge 8Km distance can be achieved
  • Central Monitoring Via Graphic application
  • Panel on single Network
  • Connectivity with BMS or Fire Alarm system
  • Two levels of user access

TECHNICAL DATA

Rated Operating Voltage                            AC100-277V
Rated Operating Frequency                       50/60Hz
Input Power                                                  8W
Emergency Power                                        5W
Operating Environment                               Damp Location
Ambient Temperature Range for
Product Application                                    0ᴼC ~ 45ᴼC
Application Standard                                  UL 924
Battery Type                                                 LiFePo₄Lithium-ion Battery
Battery Model                                              IFR21700-6000
Battery Specification                                  3.2V, 6000mAh
Charging Time                                              24 hours
Minimum Initial Continuous
Emergency Operating Time                       90 minutes
Mounting Methon                                        Wall Mounted

TYI-CB1000A UL Communication Interface Bridge Module

 

FEATURES

  • 255 Luminaire connected
  • Easy Installation available
  • Can be connect with all kinds of luminaire
  • Meets UL certification standards

TECHNICAL DATA

Rated Operating Voltage                           AC100-277V
Rated Operating Frequency                      50/60Hz
Input Power                                                 35W
Emergency Power                                       6W
Operating Environment                              Damp Location
Ambient Temperature Range for
Product Application                                    0ᴼC ~ 45ᴼC
Application Standard                                  UL 924
Battery Type                                                 LiFePo₄Lithium-ion Battery
Battery Model                                               IFR21700-3000
Battery Specification                                   9.6V, 3000mAh
Battery Capacity                                          3000mAh
Charging Time                                              24 hours
Minimum Initial Continuous
Emergency Operating Time                       90 minutes

TYI-EX-SH200A UL Evacuation Sign Light

 

FEATURES

  • Lithium Iron Phosphate (LiFeP04)
  • Universal Mounting Available
  • 3 Hours Emergency Duration
  • RAL9003

TECHNICAL DATA

Rated Operating Voltage                            AC100-277V
Rated Operating Frequency                       50/60Hz
Input Power                                                  5W
Emergency Power                                        0.5W
Operating Environment                              Damp Location
Ambient Temperature Range for
Product Application                                    0ᴼC ~ 45ᴼC
Application Standard                                  UL 924
Battery Type                                                LiFePo₄Lithium-ion Battery
Battery Model                                              IFR1865-2000
Battery Specification                                  3.2V, 2000mAh
Charging Time                                              24 hours
Minimum Initial Continuous
Emergency Operating Time                       180 minutes
Light Source Type                                        LED

TYI-FM-SRC300A UL Lighting Luminaire

 

FEATURES

  • Compliant with UL 924 for Emergency Lighting and Power Equipment
  • High Performance LED
  • Long life LEDs with 50,000hours (In Maintained Model)
  • Lithium Iron Phosphate LiFeP04)
  • Up to 2000 battery charging cycles
  • Surface and Recessed Mounting
  • RAL9003

TECHNICAL DATA

Rated Operating Voltage                            AC100-277V
Rated Operating Frequency                       50/60Hz
Input Power                                                  9W
Emergency Power                                        8W
Operating Environment                              Damp Location
Ambient Temperature Range for
Product Application                                    0ᴼC ~ 45ᴼC
Application Standard                                  UL 924
Battery Type                                                 LiFePo₄Lithium-ion Battery
Battery Model                                               IFR21700-3000
Battery Specification                                   9.6V, 3000mAh
Battery Capacity                                          3000mAh
Charging Time                                              24 hours
Minimum Initial Continuous
Emergency Operating Time                       180 minutes
Mounting Height                                          4.5 meters

TYI-SR200A UL Surface Mount Exit Light

 

FEATURES

  • Compliant with UL 924 for Emergency Lighting and Power Equipment
  • High Performance LED
  • Longlife LEDs with 50,000hours
  • Lithium Iron Phosphate (LiFeP04)
  • Up to 2000 battery charging cycle
  • 4 Years battery design life
  • Wall & Wall-Recessed Mounting
  • Auto Tet

TECHNICAL DATA

Rated Operating Voltage                            AC100-277V
Rated Operating Frequency                       50/60Hz
Input Power                                                  9W
Emergency Power                                        8W
Operating Environment                               Damp Location
Ambient Temperature Range for
Product Application                                    0ᴼC ~ 45ᴼC
Application Standard                                  UL 924
Battery Type                                                LiFePo₄Lithium-ion Battery
Battery Model                                              IFR21700-3000
Battery Specification                                  9.6V, 3000mAh
Battery Capacity                                         3000mAh
Charging Time                                              24 hours
Minimum Initial Continuous
Emergency Operating Time                       180 minutes
Mounting Height                                          4.5 meters

FM Fire Fighting System

Horizontal End Suction Fire Pump Set

 

   

FEATURES

  • For UL/ FM project (Pump, Diesel Engine, Electrical motor, Controller, Main relief valve, Pressure meter, Flow meter are all listed)

TECHNICAL DATA

Pump Capacity: 100 GPM to 8000 GPM

Pump Pressures: 40 PSI to 362 PSI

Skids Fire Pump Set

 

   

DESCRIPTION

  • For UL/ FM project (Pump, Diesel Engine, Electrical motor, Controller, Main relief valve, Pressure meter, Flow meter are all Listed)

KEY FEATURES

  • The exterior design is simple and aesthetically pleasing, with a rational layout of piping.
  • Compliant with NFPA 20 standards, with all relevant components certified by FM/UL;
  • Factory assembly
  • The prying system undergoes factory testing to ensure outstanding performance.
  • Significantly reduce on-site installation time for the users, accelerating the construction process.

Vertical Shaft Turbine Fire Pump Set

 

   

DESCRIPTION

  • For UL/ FM project (Pump, Diesel Engine, Electrical motor, Controller, Main relief valve, Pressure meter, Flow meter are all listed)

KEY FEATURES

 

Building Passive Fire Protection System

Air Fireproof & Heat insulating Finished

 

   

FEATURES

THE CORAL® (Floating Bead) Fireproof & Heat insulating Finished Air Duct.

Self-supporting integrated structure, one-stop to meet fire insulation performance

Adopted EN 1366-1 certification

TECHNICAL DATA

Lightweight and high strength:
Volume density 600kg/m³. Anti-brittle strength 10 MPa

Fire and heat insulation:
Single panel fire resistance limit 4h. Thermal conductivity 0.16 W/ (m·K)

Stable and durable
Free chloride ion content <0.1%. Softening coefficient> 80%

Safety and non-combustibility
Class A1 non-combustible. Toxicity safety level AQ1

DOWNLOAD

System Catalogs & Product Brochures .

Download our comprehensive, high-resolution product catalogs for offline review, project submittals, or client presentations.